Data Center Power Connectors: PDU and Cord Matching Guide

Match data center power connectors, IEC C13/C14 and C19/C20 cords, and common North American NEMA plugs with practical procurement checks.

Match the cord to both connection points: the source outlet and the equipment inlet. A server with a C14 inlet normally takes a C13 cord connector; when the PDU has a C13 outlet, the other end of that cord is a C14 plug. A server with a C20 inlet normally takes a C19 cord connector; a C19 PDU outlet takes a C20 plug. These are mating relationships, not complete electrical approvals.

A correct match also requires compatible supply voltage, equipment input requirements, cord-assembly ratings, regional approvals, temperature conditions, and any locking mechanism. Connector shape alone does not establish those conditions.

Identify the Outlet, Cord Ends, and Equipment Inlet

Describe each connection from the power source toward the equipment. This avoids the ambiguity of product descriptions such as “C13/C14 cable,” which may not explain which end goes where.

Connection pointWhat it doesCommon rack example
Source outlet or receptacleSupplies power to a cordC13 or C19 outlet on a rack PDU
Source-side cord plugInserts into the source outletC14 plug into C13; C20 plug into C19
Equipment-side cord connectorFits over the equipment inlet contactsC13 connector onto C14; C19 connector onto C20
Equipment inletReceives power into the equipmentC14 or C20 inlet on a server power supply

The C13/C14 and C19/C20 mating pairs appear in Eaton’s rack PDU connector reference. The same designation can appear in different mounting arrangements: a C14 interface may be an equipment-mounted inlet or the source-side plug on a jumper cord. Identify its role as well as its designation.

For example, a complete server connection can be written as:

PDU C13 outlet → cord C14 plug — cable — cord C13 connector → server C14 inlet.

The PDU’s own input connection is a separate interface. Do not order server cords from the PDU input-plug specification.

IEC C13/C14 and C19/C20 Identification Reference

Use the molded designation, equipment documentation, and manufacturer drawing to identify an interface. Shape is a useful cross-check, but it should not replace the part marking.

InterfaceContact arrangement and identification cueNormal mating interfaceTypical rack role
C13Female contacts; smaller housing with chamfered upper cornersC14PDU output outlet or equipment-side cord connector
C14Male contacts; corresponding chamfered profileC13Server or network-device inlet; source-side jumper-cord plug
C19Female contacts; larger, more rectangular profileC20PDU output outlet or equipment-side cord connector
C20Male contacts; corresponding larger rectangular profileC19Equipment inlet; source-side jumper-cord plug

Eaton’s illustrated reference shows these four interfaces and their regional rating categories. A standard C13 connector does not directly mate with a C20 inlet, and a standard C19 connector does not directly mate with a C14 inlet.

Connector ratings depend on the approval system

The same interface family can carry different current ratings under different regional approvals.

Mating pairIEC/European rating category shown in Eaton’s referenceNorth American rating category shown in Eaton’s reference
C13/C1410 A, 250 V15 A, 250 V
C19/C2016 A, 250 V20 A, 250 V

These are reference categories—not a guarantee that every cord with those ends carries the maximum listed current. Use the applicable approval and rating of the actual purchased assembly.

The distinction is visible in component-level documentation. SCHURTER’s 4795 C19 connector lists an IEC rating of 16 A at 250 VAC, 50 Hz, and a UL/CSA rating of 20 A at 250 VAC, 60 Hz. Those are ratings for that connector under the stated approvals and conditions, not an automatic rating for a cord assembled around it.

A 250 V marking also does not identify the voltage actually present at a PDU outlet. Confirm the configured supply voltage and the equipment’s permitted input range separately.

Match the Cord to Both Ends

Choose the source-side plug from the outlet and the equipment-side connector from the inlet. The following table identifies physical connection paths; each selection still requires the electrical and installation checks below.

Source outletEquipment inletCord ends, source → equipmentSelection condition
IEC C13IEC C14C14 plug → C13 connectorStandard matching pair at each end
IEC C19IEC C20C20 plug → C19 connectorStandard matching pair at each end
IEC C19IEC C14C20 plug → C13 connectorValid mixed-end cord arrangement; retain the assembly’s own current limit
NEMA 5-15RIEC C145-15P plug → C13 connectorEquipment must accept the actual supply voltage
NEMA 5-20RIEC C145-20P plug → C13 connectorDo not infer a 20 A cord rating from the source plug
NEMA L6-20RIEC C20L6-20P plug → C19 connectorVerify equipment voltage requirements and the complete cord rating
NEMA L6-30RPDU with an L6-30P inputPDU’s specified L6-30P input cordThis is the facility-to-PDU connection, not a server jumper

The IEC pairings and NEMA plug/receptacle designations are shown in Eaton’s connector reference. Eaton also lists commercial C20-to-C13 and L6-20P-to-C19 cord arrangements.

A mixed-end cord does not inherit the larger connector’s rating

A C20-to-C13 cord can connect a C19 PDU outlet to a C14 equipment inlet. It does not make the equipment connection a 20 A path.

For example, Eaton’s P032-007 is specified as a C20-to-C13 cord rated 15 A, 100–250 V, with 14 AWG conductors and a length of 7 ft (2.13 m). The C20 end does not override the published 15 A assembly rating. That product rating also should not be transferred to a different cord with similar-looking ends.

The reverse situation—a C13 source outlet supplying equipment with a C20 inlet—requires particular care. A manufacturer-supplied C14-to-C19 assembly may exist, but its existence does not establish that the equipment is suitable for the lower-rated source path. Eaton lists a 15 A C14-to-C19 cord among its PDU accessories; selection still depends on the equipment’s permitted input configuration and current requirement.

Do not use an adapter merely to bypass a connector mismatch without resolving why the equipment and source use different interfaces.

Common North American NEMA Connections

The following configurations are common in North American rack-power connections. They are not a global receptacle reference.

In NEMA designations, P identifies a plug, R identifies a receptacle, and an initial L identifies a locking configuration. Thus, L6-30P is a locking plug, while L6-30R is its corresponding receptacle.

NEMA configurationDevice ratingMechanical styleCorresponding connection
5-1515 A, 125 VACStraight blade5-15P plug and compatible receptacle
5-2020 A, 125 VACStraight blade5-20P plug and 5-20R receptacle
L5-2020 A, 125 VACLockingL5-20P and L5-20R
L5-3030 A, 125 VACLockingL5-30P and L5-30R
L6-2020 A, 250 VACLockingL6-20P and L6-20R
L6-3030 A, 250 VACLockingL6-30P and L6-30R

Eaton’s wiring-device catalog gives these device ratings; its rack PDU reference illustrates the plug and receptacle configurations.

Keep device voltage ratings separate from nominal operating voltage. Eaton’s rack reference associates common 5-series applications with 120 V and common L6 rack applications with 208 V, while the corresponding wiring devices are rated 125 V and 250 V respectively. Neither number alone identifies the actual voltage at a particular outlet.

Do not substitute L5 for L6, or a 20 A locking configuration for a 30 A locking configuration. Match the full designation rather than only the current number or the presence of curved blades.

Separate PDU Input Matching From PDU Output Matching

A rack PDU can have one connector family at its input and several different output interfaces.

For a concrete example, Eaton’s PDUMVR30HVNETLX product page specifies:

  • An L6-30P input plug.
  • Twenty C13 output outlets.
  • Four C19 output outlets.
  • A 208/230 V operating specification and a 24 A PDU current rating.

Its connection paths are therefore:

Facility L6-30R receptacle → PDU L6-30P input plug → PDU.

PDU C13 outlet → C14-to-C13 cord → equipment C14 inlet.

PDU C19 outlet → C20-to-C19 cord → equipment C20 inlet.

The L6-30 input designation does not make every output outlet a 30 A connection. Likewise, the presence of both C13 and C19 outlets does not establish different output voltages or imply voltage conversion. Use the exact PDU model’s electrical specifications and installation instructions to establish what each outlet supplies.

This distinction lets purchasing teams answer two different questions without mixing them: “Will the PDU connect to the facility receptacle?” and “Which cords connect the equipment to the PDU?”

Check Electrical and Mechanical Conditions Before Ordering

Supply voltage and equipment input

Record the actual supply voltage and frequency, then compare them with the installed power supply’s nameplate and manual. Use the power-supply model, not only the server chassis model: a chassis may be offered with different power-supply options.

Do not assume that a C14 or C20 inlet means the equipment accepts every voltage used with that connector family. If the power supply’s permitted voltage range is unknown, connector identification alone cannot resolve suitability.

Complete cord-assembly rating

Obtain the manufacturer’s rating for the complete cord, including its applicable regional approval. Record the conductor size and jacket type, but do not derive an approved assembly rating from AWG alone.

Eaton’s locking-cord catalog, for example, lists C14-to-C13 assemblies at both 10 A with 18 AWG conductors and 15 A with 14 AWG conductors. Similar endpoint designations therefore do not establish identical cord ratings.

The cord rating must suit the equipment’s required input current under the intended operating conditions. Outlet-group capacity, branch-circuit loading, protective-device selection, and redundancy behavior remain separate checks; a connector table does not resolve them.

Temperature and inlet type

Check the equipment’s specified connector type and temperature requirements. Do not replace a specified higher-temperature connector with a C13 merely because the interfaces appear similar.

Also distinguish contact-temperature conditions from ambient-temperature limits. SCHURTER’s 4795 documentation identifies a 70°C pin-temperature condition and separately lists an allowable operating-temperature range of −25°C to 70°C. These are product-specific conditions, not universal temperature limits for every C19 cord or every rack installation.

Locking and retention compatibility

A locking IEC cord needs a compatible retention system. “Locking C14” or “locking C20” is not enough information to establish that a particular PDU will engage the latch.

Eaton specifies P-Lock C14 cords for P-Lock-compatible C13 or C39 outlets, and P-Lock or P-Lock Lite C20 cords for compatible C19 or C39 outlets. Verify the exact cord and PDU combination rather than assuming interchangeability between retention systems.

Some combination outlets accept more than one plug type. Eaton’s C39 outlet, for example, accepts both C14 and C20 plugs. Treat that as a documented feature of the specified outlet—not a property of ordinary C13 or C19 outlets.

Length, orientation, and service access

Measure the intended routed path, including cable-management arms and necessary service movement. Specify the shortest practical length that avoids tension and still allows the equipment to be serviced.

For right-angle connectors, approve a manufacturer drawing showing cable-exit direction relative to the inlet and adjacent hardware. “Left,” “right,” “up,” and “down” can be ambiguous when supplier drawings use different viewing directions.

Confirm that the connector body, latch, and cable bend do not obstruct adjacent outlets, power-supply handles, or removal access.

Procurement Checklist

Create one line item for each distinct cord assembly. Use the following fields to make the purchase specification reviewable.

FieldWhat to record
Equipment identificationDevice model, installed PSU model, and inlet designation
Source identificationPDU model, outlet designation, and assigned outlet or group
Source-side cord endExact plug designation and required locking system
Equipment-side cord endExact connector designation, retention requirement, and exit orientation
Electrical conditionsActual supply voltage and frequency; equipment’s permitted input and required current
Assembly ratingsPublished cord current and voltage ratings, applicable approvals, and manufacturer part number
Cable constructionConductor count and size, jacket designation, and specified temperature conditions
RoutingRequired length, connector clearances, support, and service movement
Feed identificationEquipment PSU label, PDU asset ID, outlet ID, and A/B feed designation where applicable
QuantityNumber of verified connections using that exact assembly

For redundant power supplies, document each connection independently. Different cord colors can help trace A and B feeds, but color does not establish that the upstream power paths are independent. Eaton presents color coding as an identification aid for dual-source installations, not as proof of redundancy.

Release the order only when both endpoints, the complete assembly rating, and the equipment’s input requirements are known. Where a marking is unreadable or a datasheet omits a material condition, obtain the missing manufacturer documentation rather than filling the gap from appearance alone.